500MS HOA Board of Directors, Tyco Q&A

1. Are the unit alarms tied to the main common area alarm? No

2. If a unit smoke detector goes off, does the loud main common building alarm go off automatically? No All unit alarms are not tied into common alarm panel, which is per the original design, do the other unit alarms go off? No

3. If a unit sprinkler head detects heat and goes off, does the main loud common building alarm go off? Yes

4. If a unit sprinkler head goes off, do individual alarms go off? No

5. If the main building alarm goes off, do the individual unit alarms go off? No

6. If the main common building alarm goes off, does Tyco immediately call the Fire Department? Yes

7. If a unit sprinkler head detects heat and goes off, does Tyco immediately call the Fire Department? Yes

8. If a smoke detector in an individual unit goes off, does Tyco immediately call the Fire Department? No

9. On the day of our fire in September, did Tyco immediately call the Fire Department? If so, what time? Can Tyco give us a time stamp? On the day of the fire at 12:44:09pm an alarm came in from your control indicating a Sprinkler Water flow alarm; we called the Orange County Dispatch & the Fire Department was dispatched; we then called the call list provide by Berkeley